FANS, a.s. it now supplies a cooling tower with a total of fourteen CTF 200 cells, divided into two cooling circuits - Loop 1-10 cells and Loop 2-4 cells), the arrangement of these towers is back-to-back. The delivery is for the German company Linde and is intended for a new ethylene plant in Nizhnekamsk. We are preparing the delivery for June 2020.

Linde Job No. 3110 BR4N Nizhnekamsk 2020

Technical parameters:

Winter season:      inlet 45 ° C outlet 25 ° C

Summer:               inlet 45 ° C outlet 30 ° C

         Wet bulb temperature 21.3 ° C

LOOP flow 1     25 700 m3 / h     LOOP flow 2    8 710 m3 / h